Partial discharge activity due to particle movement in SF6 gas filled electrode gap under different voltage profiles
Published in Institute of Electrical and Electronics Engineers Inc.
2018
Volume: 25
   
Issue: 4
Pages: 1429 - 1438
Abstract
The levitation voltage of the conducting/non conducting particle in the SF6 gas filled electrode gap is high under DC voltage compared with the AC voltage. The levitation voltage increases with frequency of the supply voltage. Particle levitation voltage marginally increases with increase in THD of the harmonic AC voltage. The levitation voltage of the particle increases as and when the barrier is moved towards the high voltage electrode. No polarity dependency is observed on levitation voltage under DC voltages. Percentage of filler content in epoxy nanocomposites has high impact on levitation voltage of the particle. The analysis of levitation voltage with epoxy nanocomposites indicates that up to 3 wt% of MgO added specimen, the levitation voltage is high and above which a marginal reduction in levitation voltage of particle in SF6 gas medium is observed. The UHF signal magnitude caused by the particle movement process increases with the applied voltage. Also, the extinction voltage of particle movement is lower than the levitation voltage. Also, with increase of applied voltage, on levitation, the magnitude of UHF signal increases. However, on reducing the applied voltage, the UHF signal magnitude is much higher than onward application of voltage. This characteristics is almost the same under AC and DC voltages. The FFT analysis of UHF signal formed due to particle under AC and DC voltages, at the point of inception has dominant frequency at around 1 GHz. When the applied voltage is increased, especially under DC voltages, the FFT analysis of UHF signal formed indicates energy content in the band 2-3 GHz is increased, indicating indirectly, the rate of charge transfer due to particle movement with opposite electrode is high under DC voltages. The FFT analysis of UHF signal formed by non-conducting particle under high frequencies have the energy content increased in the range 2-5 GHz. PRPD analysis indicates that PD activity is observed in the entire phase of the applied AC voltage, irrespective of harmonics and THDs. The number of PD occurrence is high where the rate of rise of supply voltage is high. © 1994-2012 IEEE.
About the journal
JournalData powered by TypesetIEEE Transactions on Dielectrics and Electrical Insulation
PublisherData powered by TypesetInstitute of Electrical and Electronics Engineers Inc.
ISSN10709878
Open AccessNo
Concepts (22)
  •  related image
    Charge transfer
  •  related image
    Electrodes
  •  related image
    Elementary particles
  •  related image
    Fast fourier transforms
  •  related image
    Harmonic analysis
  •  related image
    Hvdc power transmission
  •  related image
    Magnesia
  •  related image
    Nanocomposites
  •  related image
    Optical variables measurement
  •  related image
    Partial discharges
  •  related image
    SF6 INSULATION
  •  related image
    SULFUR HEXAFLUORIDE
  •  related image
    Uhf devices
  •  related image
    CONDUCTING PARTICLES
  •  related image
    Epoxy nanocomposites
  •  related image
    HARMONIC VOLTAGES
  •  related image
    HIGH VOLTAGE ELECTRODES
  •  related image
    PARTIAL DISCHARGE ACTIVITY
  •  related image
    PARTICLE MOVEMENT
  •  related image
    SF6 GAS
  •  related image
    UHF SIGNAL
  •  related image
    Signal analysis