Abstract
With steady increase in the wind power penetration, regulatory standards for grid connection have evolved. The regulatory standards require the wind generation system to ride-through disturbances such as faults and support the grid during such events. This fault ride-through capability is determined by its corresponding critical clearing time (CCT). Conventionally, determination of CCT involves a large number of trial and error iterations that requires repetitive runs of related time-domain simulations. A method is proposed in this paper to compute CCT using non-conventional approach that avoids running related time-domain simulations several times. This work proposes a method to enhance the fault- ride through capability of squirrel cage induction generator based wind farms using Dynamic Voltage Regulator (DVR). The DVR controller is designed to work under fault conditions, which improves the critical clearing time of the system by injecting real power required by the system. The detailed simulation results are presented. © 2012 IEEE.
About the journal
Journal2012 11th International Conference on Environment and Electrical Engineering, EEEIC 2012 - Conference Proceedings
Open AccessNo
Concepts (12)
  •  related image
    CRITICAL CLEARING TIME
  •  related image
    CRITICAL SPEED
  •  related image
    DYNAMIC VOLTAGE RESTORER (DVR)
  •  related image
    FAULT-RIDE THROUGH (FRT) CAPABILITY
  •  related image
    Squirrel cage induction generators
  •  related image
    Electric fault currents
  •  related image
    Electric utilities
  •  related image
    Electrical engineering
  •  related image
    Power converters
  •  related image
    Time domain analysis
  •  related image
    Wind power
  •  related image
    Voltage regulators