Transform ers are required to demonstrate the ability to withstand short circuit currents. Over currents due to short circuit can cause winding deformation. A new method of testing and analyzing winding deformation online without untanking is presented in this paper. A study of alternate excitations to detect winding deformation is made .A comparison of Fourier transform and Wigner-Ville Distribution methods of analysis is carried out. © 2005 IEEE.