Steady-state error estimation in distance relay for single phase to ground fault in series-compensated parallel transmission lines
Ch R. Venkatesh,
Published in Institution of Engineering and Technology
2014
Volume: 8
   
Issue: 7
Pages: 1318 - 1337
Abstract
Distance relay zone reach setting demands for the knowledge of transient and steady-state error to ensure secure operation. This study addresses the estimation of steady-state error which will be encountered by conventional distance relay protecting series-compensated parallel transmission lines (SCPTLs). Different factors like, remote-end in-feed, varying levels of series compensation and fault resistance are taken into consideration to arrive at generalised expressions for transposed SCPTL. These expressions can be used to estimate steady-state error in positive sequence impedance estimation which will be encountered by healthy and faulty line relays, both with and without mutual compensation. Comprehensive analysis is done using two different tower configurations for each of the above-mentioned factors, both with and without mutual compensation to analyse healthy and faulty line relay behaviour. © The Institution of Engineering and Technology 2014.
About the journal
JournalIET Generation, Transmission and Distribution
PublisherInstitution of Engineering and Technology
ISSN17518687
Open AccessNo
Concepts (14)
  •  related image
    Electric grounding
  •  related image
    Electric power system protection
  •  related image
    Electric relays
  •  related image
    Errors
  •  related image
    Transmission line theory
  •  related image
    Comprehensive analysis
  •  related image
    Distance relay
  •  related image
    FAULT RESISTANCES
  •  related image
    PARALLEL TRANSMISSION LINES
  •  related image
    SEQUENCE IMPEDANCES
  •  related image
    Series compensation
  •  related image
    SINGLE PHASE TO GROUND FAULTS
  •  related image
    Steady state errors
  •  related image
    Error compensation