Smart trip logic for smart grids to block distance relay maloperation - Implementation and validation
Ch R. Venkatesh,
Published in
2013
Abstract
Zone 1 reach setting of a distance relay depend upon many factors, such as, dc offset in current signals, loading effect, fault resistance in the presence of in-feed from remote end and also capacitive voltage transformer (CVT) transients. All these factors are taken care of except for CVT transients, which is dealt either by reducing zone 1 reach or by providing a fixed time delay in today's intelligent electronic devices (IED). This paper proposes a new and simple logic to prevent numerical distance relay mal-operation by zone 1 element due to CVT transients without sacrificing zone 1 reach. This is achieved by providing adaptive time delay by actually monitoring the CVT transients in time domain. The proposed logic is validated in real time by incorporating the proposed logic along with positive sequence polarized distance relay model in field programmable gate array (FPGA). © 2013 IEEE.
About the journal
Journal2013 IEEE Innovative Smart Grid Technologies - Asia, ISGT Asia 2013
Open AccessNo
Concepts (15)
  •  related image
    CAPACITIVE VOLTAGE TRANSFORMER
  •  related image
    CURRENT SIGNAL
  •  related image
    Distance relay
  •  related image
    FAULT RESISTANCES
  •  related image
    FIXED TIME DELAYS
  •  related image
    INTELLIGENT ELECTRONIC DEVICE
  •  related image
    LOADING EFFECTS
  •  related image
    NUMERICAL DISTANCE RELAYS
  •  related image
    Electric relays
  •  related image
    Field programmable gate arrays (fpga)
  •  related image
    Smart power grids
  •  related image
    Time delay
  •  related image
    Transients
  •  related image
    Variable speed transmissions
  •  related image
    Loading