Header menu link for other important links
X
Location of partial discharges in transformers
V. Jayashankar
Published in
2003
Pages: 620 - 623
Abstract
A matched filter approach is proposed for the location of a partial discharge within a winding. The approach is very general and does not need isolation of the capacitively transferred components. Simulations are performed on a lumped parameter model of a layer winding to prove the feasibility of the method. Experiments are also performed on a layer winding in order to validate the method. It is possible to extend the method to the determination of location of PD during impulse tests.
About the journal
JournalConference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
ISSN00849162
Open AccessNo
Concepts (6)
  •  related image
    Computer simulation
  •  related image
    ELECTRIC FILTERS
  •  related image
    Electric transformers
  •  related image
    Electric windings
  •  related image
    MATCHED FILTERS
  •  related image
    Partial discharges