Abstract
It is possible to estimate the location of the fault based on a study of the resonant frequencies of the winding current. It is shown that the nearest neighbourhood rule based on a clustering approach provides a good framework for fault location. Additional signal acquisition in the form of the tank current can considerably simplify the identification of a fault to ground. Experimental investigations are performed in order to identify and locate breakdown in windings.